Type 1 SPDs for main distribution
Devices declared for partial lightning current at the origin of an installation, rated by impulse current rather than nominal discharge alone.
AC, DC & PV Surge Protectors
Check product standards and documentation for surge protection devices shipped to Saudi Arabia.
HS 8536
Protective apparatus for circuits up to 1000 V. Devices for higher voltages fall under 8535. The Saudi code runs longer than four digits and is confirmed from the specification, not from the product name.
IEC 61643 series where applicable; model grouping
Candidate review point, not a declaration that this route applies. Confirmed against the current regulation and model scope before anything is claimed.
Type 1/2/3 SPD, DC/AC and PV applications
What the assessment reads the product as, which decides the evidence it asks for.
The core set. On this family the file also turns on up, In, Imax ratings, voltage class, SPD type. Which further documents apply varies with the confirmed classification and the model scope, so the full list is issued per file rather than per category.
Illustrative layout only — not an issued certificate, and not a reproduction of one. Certificates are issued by approved conformity assessment bodies, not by BenzilaCert.
Typical files in this product family and the support they call for. Illustrative scenarios, not completed engagements.
An AC surge protection device, where the declared impulse ratings and voltage protection level belong to the assembled device including its disconnector.
A photovoltaic or DC variant, which is a separate declaration and is not covered by AC evidence even where the housing is shared.
Send the Saudi HS Code if you have it, the product specification and a commercial invoice, and we will come back with the likely route and what is missing.
* Where applicable. Timelines and charges shown are indicative and subject to documentary review, and government and SADAD fees are separate from conformity body, testing and consultancy charges. The applicable Saudi regulation and the exact HS code must be confirmed from the product specification against the current SABER and ZATCA classification.
BenzilaCert is an independent consultancy providing application and documentation support. It is not SASO, SABER or a certificate-issuing authority, and does not issue conformity certificates.
Each family below is declared for a different position in the installation, and each carries its own impulse ratings and its own evidence.
Devices declared for partial lightning current at the origin of an installation, rated by impulse current rather than nominal discharge alone.
Devices for downstream boards, defined by nominal discharge current, maximum discharge current and declared voltage protection level.
Point-of-use protection fitted close to the equipment. Assessed on its own ratings, not on the upstream device it works with.
Devices declared for DC circuits and PV string voltages, where the DC withstand behaviour is a separate declaration from AC.
Protection for communication circuits, evidenced against a different standard family from power SPDs.
A device declared to interrupt overcurrent is a protective device of a different kind. That route is on our circuit breakers page.
An SPD and a breaker are not the same kind of protection
Six factors that separate one SPD file from another. Each is read from the declared ratings, not from the housing.
| Factor | Why it changes the answer |
|---|---|
| SPD type | Type 1, Type 2 and Type 3 devices are declared for different installation positions and tested differently |
| AC, DC or PV application | DC and photovoltaic devices are separate declarations and are not covered by AC evidence |
| Impulse and discharge ratings | Iimp, In and Imax are the primary ratings and are tested, not derived from the housing |
| Voltage protection level | The declared Up is what the protected equipment is selected against, so it is read closely at review |
| Maximum continuous operating voltage | Uc defines the network the device may be used on and separates otherwise identical models |
| Replaceable module or fixed unit | A base and plug-in module arrangement is declared as a system, including which modules fit which base |
We do not publish an HS code for surge protection devices, because the code follows the device specification rather than the category. Power SPDs, signal-line protectors and parts can classify differently, and the classification is what determines the applicable regulation. It is confirmed per family — see our HS code check.
What may apply to an SPD file, and what is confirmed per family rather than across the category.
Where the confirmed classification falls under an applicable Saudi technical regulation, a surge protection device generally needs a product certificate registered on SABER, followed by a shipment certificate for each consignment. The product certificate is issued by an approved conformity assessment body against the technical file and the test evidence.
SPD standards are divided by application — low-voltage AC power, photovoltaic and DC circuits, and telecommunication and signal lines. A manufacturer selling across those applications is preparing more than one declaration, and evidence from one application does not support another even where the housing and the model number family are shared.
Whether the IECEE route is available for a given device depends on the current national recognition scope. It does not follow automatically from the product being an SPD, so we confirm it against the current published scope before relying on it.
The declared ratings belong to the finished device
Checks an SPD assessment commonly draws on. Which apply depends on the declared type and application, and the standard part the regulation names.
| Check | What it looks at |
|---|---|
| Nominal discharge current | Repeated impulse withstand at the declared In |
| Maximum discharge current | Single impulse withstand at the declared Imax |
| Impulse discharge current | Behaviour at the declared Iimp, for Type 1 devices |
| Voltage protection level | Measured residual voltage against the declared Up |
| Follow current interruption | Behaviour after conduction on devices containing spark-gap technology |
| Thermal stability and disconnector operation | End-of-life behaviour and the internal disconnector |
| Status indication | Operation of the indicator or remote contact as declared |
| Dielectric strength and insulation | Insulation between terminals and to earth under applied test voltage |
Testing is carried out by laboratories accredited for the relevant tests. Impulse testing consumes samples — devices are tested to and past their limits — so sample quantities are agreed with the laboratory before a programme starts.
What an SPD submission is built from. Module compatibility and the DC variants are the parts most often missing.
Send the model list with In, Imax, Iimp, Up and Uc as declared, plus the reports you hold. We will map the evidence against the declarations model by model.
Five steps from the family split to certified consignments.
Type 1, Type 2 and Type 3 devices, and the AC, DC and signal-line variants, are split first. They are declared for different positions and tested differently.
Confirm the Saudi HS code per family, then the applicable technical regulation and which standard part it names for the device in question.
Check that the reports support the declared In, Imax, Iimp, Up and Uc for every model on the list, and identify the remaining testing.
Prepare the technical file with the model list and module compatibility detail, then submit for assessment by the approved certification body.
Each consignment is applied for against the product certificate, with the invoice models — bases and modules alike — matching the certified list.
Separate the government fees from the body, testing and service charges before comparing quotations.
Four things move the cost of an SPD programme: how many type and application families the range splits into, how many voltage variants and modules the certified list has to carry, whether impulse testing is still needed and at what ratings, and the number of consignments needing shipment certificates.
Government and SADAD fees, conformity body charges, laboratory testing and service charges are separate lines and are quoted separately. Our SABER certificate cost page sets out how those lines work. We do not publish a flat price or a guaranteed turnaround for an SPD file, because both depend on the family split and the testing gap.
Six issues we see repeatedly on surge protection submissions.
The voltage protection level is how an installer selects the device. A declared Up the report does not support is one of the fastest ways to lose a file.
A Type 1 declaration needs impulse current evidence at the declared Iimp. Discharge current testing for a Type 2 device does not establish it.
DC and photovoltaic devices are separate declarations with separate evidence. A PV variant shipped under an AC certificate is uncertified.
Replacement modules ship as spares in volume. Where the module is not on the certified list, the spares consignment stalls even though the base is certified.
A varistor datasheet is not an SPD test report. The ratings belong to the finished device including its disconnector and housing.
In, Up and Uc are read off the device body against the technical file. Devices marked only with a model number raise a query at review.
The devices an SPD sits beside, and the certificates a range ends up on.
Type grouping, SPDs against breakers, PV variants, replacement modules, existing reports and the shipment stage.
Where the confirmed Saudi HS code for the device falls under an applicable technical regulation, an SPD generally needs a product certificate registered on SABER and then a shipment certificate per consignment. It follows the classification of the device rather than the category name, so it is confirmed per family.
They are declared for different installation positions and tested against different impulse regimes, so they are normally evidenced as separate families. Voltage variants within one family that share construction and standards can often be grouped.
Both protect, but they are different products on a certification file. A breaker interrupts overcurrent in the power path at a rated breaking capacity; an SPD diverts transient energy and is defined by impulse ratings and a declared voltage protection level. The evidence for one says nothing about the other.
Generally yes. DC and PV devices behave differently under fault conditions and are declared and tested separately, even where an AC model looks mechanically identical. A PV variant has to appear on a certificate that covers its declared DC ratings.
They need to be on the certified model list if they are shipped. Modules sold as spares are products in their own right at the border, and a module absent from the list is treated as uncertified when the invoice is checked.
Possibly in part. Reports to the standards the applicable regulation names, from a laboratory accredited for those tests, may support the file. Gaps are usually about whether the reports cover the declared impulse ratings and the voltage protection level for every model, rather than about the laboratory.
The commercial invoice and packing list with model numbers exactly as certified, including bases and modules, the product certificate reference, and the transport and origin documents. Our SABER documents checklist sets out the full list.
Send the model list with declared In, Imax, Iimp, Up and Uc, the applications you sell into, and any test reports you hold. We will review how the families split and what evidence is missing.
Tell us about the devices you ship, their declared ratings, and whether you also sell DC, PV or signal-line variants. We reply within one business day with the likely route and what to send next.